DRS Low Differential Pressure TransmitterLow range differential pressure sensor with rangeable 4-20mA current loop or amplified voltage output signal in pressure ranges from 1.6mb up to 6 bar differential The DRS differential pressure transducer can be used with either non-condensing clean gases or low viscosity liquids & condensing dirty gases with the silicone oil filled option. The digital electronics can easily be configured to set-up a turndown range of up to 5 to 1, compound range, elevated zero, square root output for flow measurement, customer specified non-linear output, filter jump out and RC time constant adjustment.
Technical Summary Pressure Ranges: from 1.6 mb up to 6 bar differential Accuracy: ±0.25% FS Output Signal: Fully configurable 4 to 20 mA current or amplified voltage output available Electrical Connection: Large DIN 43650 plug & socket, IP65 protection rating Pressure Connection: 1/8 BSP female Special Features: Rangeable turndown of 5 to 1 for each base range range Special Options: Non-linear output signals, square root, 3/2, 5/2 type, high overload protection with XD (gas) and WS versions (liquids) Related Products Differential pressure sensor with ranges higher than 6 bar Differential pressure sensor with ranges below 1.6 mbar (160 Pa) More differential pressure instrumentation Resources Look up definitions for pressure sensor parameters Engineering unit conversions for pressure Download Product Information