High precision pressure transmitter with an accuracy of 0.05%FS BSL NLHR and digitally adjustable pressure ranges from 170mb up to 35 bar gauge & absolute

Quote | PDF | Spec | Links

The DMP 331i high accuracy pressure transmitter sensor uses a silicon strain gauge diaphragm housed in an oil filled capsule and the repeatable & low hysteresis properties of silicon are exploited by the digital amplifier with 16 bit A/D conversion to provide a highly precise pressure measurement over the operating temperature range.

The DMP-331i high accuracy pressure transmitter is available with ATEX approval for intrinsically safe use in hazardous environments

 

Technical Summary

Pressure Ranges: 0.17 up to 35 bar gauge or absolute

Accuracy: 0.05% full scale BSL NLHR

Output Signal: 4-20mA or 0-10V dc output signal

Electrical Connections: DIN plug, Binder connector, M12 x 1 connector

Pressure Connections: G1/4, G1/2, DIN3852 and EN837, G1/2 flush, G1/2 open port, 1/4NPT male, 1/2NPT male

Media Compatibility: SS316Ti pressure port, SS316L diaphragm, FKM or NBR internal seals 

Special Features: Turndown adjustment of pressure range via RS232 interface 

Special Options: ATEX approval for Intrinsic safety II 1 G EEx ia IIC T4


Related Products

High precision pressure transmitter for measuring above 50 bar (750 psi) 

More high accuracy pressure instrumentation


Resources

Pressure transmitter terminology

Convert pressure units


Download Product Information

DMP331i data sheet DMP331i data sheet

DMP331i operating manual DMP331i operating manual

Hazardous Area installation manual Hazardous Area installation manual


Request a Quote
Pressure Range:
Output Signal:
Electrical Connection:
Pressure Connection:
Seals:
RS232 interface ready (Binder 7 pin only) :
Configuration software and RS232 cable:
ATEX IS Approval:
Quantity:
Your Name:
Your Email:
Comments:

Home > Your Application > Vacuum Pressure > Vaccuum Pressure Transmitters - Milliamp Signal

Request Info | Ask a Question

Site Last Updated:  20/11/08

Tools
Pressure Conversion


Equals

Temperature Conversion


Equals

IP Ratings Explained

I P

First Digit (Solids)
No protection

Second Digit (Liquids)
No protection

Resources

Pressure Measurement Glossary - Find explanations of terminology used for specifying and using pressure instruments

Pressure Unit Conversion - Look up conversion factors or select a conversion table for a particular pressure unit

Pressure Sensor Specification - Select parameters with PSAT to generate a spec for your own use or to submit as an enquiry

Contact

Help:  Request Info

         Ask a Question

News
RSS News Feed
RSS

©2008 SensorsONE Ltd, All Rights Reserved.